Hardware Installation
Hardware Installation
Safety Precautions
Read the following before installing or operating the Power Distribution Units (PDU)
Use only the supplied hardware to attach the mounting brackets.
Intended to be used in a location having equipotential bonding (such as a telecommunication center, a dedicated computer room
Installation instructions that require verification of the PROTECTIVE EARTHING connection of the socket-outlet by a SKILLED PERSON
Do not use extension cords or adapters with this PDU
Never install a PDU or associated wiring or equipment during a lightning storm
Ensure that the power cord, plug, and socket are in good condition
Hardware Installation
Place on a Flat Surface in the Computer Room
Suitable for installation in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA 75. (Marking or Instruction) The PDU can be secured using the screws and rack ears included in the accessory kit
Peut être installé dans des salles de matériel de traitement de l’information conformément à l’article 645 du National Electrical Code et à la NFPA 75. (Marking or Instruction)
Step 1: Attach the Rubber Footpads to the bottom corners of the PDU. The Rubber Footpads help secure the PDU and protect it from vibration and shock when stacked.
Step 2: Use (M4 x 6)screws to attach the rack ears to both sides of the device. This will allow you to position the PDU on any flat surface.
Step 3: Attach the bracket with 4(T4x19) to secure the PDU firmly to the flat surface.
Rack Mount
Securely attach the device with rack ears onto the rack using screws. Make sure it is securely attached and not wobbling.
(Due to different rack specifications, we have not included rack mounting screws. We recommend using M5 x 12 screws along with washers for securing.)
Power On Device
Connect the Power cord to the front of the PDU, and then plug it into the power outlet.
Last updated